Analysis of Phosphate (PO43-) and Total Iron (Fe) Concentrations in the Main Cooling Water System of Keramasan Combined-Cycle Power Plant
DOI:
https://doi.org/10.68712/zpvssq65Keywords:
Main Cooling Water, Phosphate Concentration, Total Iron, Combined-Cycle Power Plant, Spectrophotometry UV-VisAbstract
Maintaining water chemistry in cooling circuits is critical for controlling mineral scaling and electrochemical corrosion in power generation systems. This study evaluated the residual concentrations of phosphate (PO43-) and total iron (Fe) in the open-recirculating Main Cooling Water (MCW) system at Keramasan Combined-Cycle Power Plant (CCPP), Palembang, South Sumatra. Water samples were monitored spectrophotometrically across 10 monitoring days between January 20 and February 6, 2025. Phosphate levels were quantified via the ascorbic acid-molybdenum blue method, while total iron was determined using the 1,10-phenanthroline method. The analytical results showed that phosphate concentrations ranged from 0.28 to 2.82 mg/L, remaining consistently below the established operational threshold of 6.0-11.0 mg/L. A pronounced decrease in phosphate was observed following the temporary cessation of corrosion inhibitor dosing and concurrent system blowdown during plant maintenance. Conversely, total iron concentrations fluctuated between 0.02 and 0.32 mg/L, successfully complying with the maximum permissible quality standard (< 2.0 mg/L). The sub-optimal phosphate levels indicate an insufficient passivation barrier against metallic corrosion, emphasizing the need to optimize chemical injection dosage and conduct routine upstream monitoring of raw river water to preserve system integrity and thermal efficiency.
Downloads
Downloads
Published
Issue
Section
License
Copyright (c) 2026 Dinar Adelia, Ade Oktasari (Author)

This work is licensed under a Creative Commons Attribution-NonCommercial-ShareAlike 4.0 International License.